Actual signals and parameters 209
1503 AO1
CONTENT
MAX
Defines the maximum value for the signal selected with
parameter
. See the figure for
parameter
-
x…x
Setting range depends on the parameter
setting.
-
1504 MINIMUM AO1 Defines the minimum value for the analog output signal AO.
See the figure for parameter
.
0.0 mA
0.0…20.0 mA
Minimum value
1 =
0.1 mA
1505 MAXIMUM
AO1
Defines the maximum value for the analog output signal AO.
See the figure for parameter
.
20.0 mA
0.0…20.0 mA
Maximum value
1 =
0.1 mA
1506 FILTER AO1
Defines the filter time constant for analog output AO, ie, the
time within which 63% of a step change is reached. See the
figure for parameter
.
0.1 s
0.0…10.0 s
Filter time constant
1 = 0.1 s
16 SYSTEM
CONTROLS
Parameter view, Run enable, parameter lock etc.
1601 RUN ENABLE
Selects a source for the external Run enable signal.
NOT SEL
Allows the drive to start without an external Run enable
signal.
0
DI1
External signal required through digital input DI1. 1 = Run
enable. If Run enable signal is switched off, the drive will not
start or coasts to stop if it is running.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
COMM
Fieldbus interface as the source for inverted Run enable
signal (Run disable), ie, Control word
bit 6 (with ABB drives profile
bit 3). The
Control word is sent by the fieldbus controller through the
fieldbus adapter or embedded fieldbus (Modbus) to the
drive. For the Control word bits, see sections
on page
and
on page
7
DI1(INV)
External signal required through inverted digital input DI1. 0
= Run enable. If Run enable signal is switched on, the drive
will not start or coasts to stop if it is running.
-1
DI2(INV)
See selection
.
-2
DI3(INV)
See selection
.
-3
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...