Actual signals and parameters 57
DI3
See selection
3
DI4
See selection
4
DI5
See selection
5
DI1(INV)
Inverted digital input DI1. Defines the inverted digital
input DI1 as the control for dry run protection.
6
DI2(INV)
See selection
7
DI3(INV)
See selection
8
DI4(INV)
See selection
9
DI5(INV)
See selection
10
WITH_P60.16
See parameter
11
6016
MIN LOAD
CURRENT
Defines the minimum load current for dry run
protection of inverter. When actual motor current is
less than this value for the time defined in 6017 DRY
RUN TRP TIME, the inverter trips due to
.
1 = 1 A
0...2 * Drive
rating A
Current
0
6017
DRY RUN TRP
TIME
Allows inverter to wait for this time to trip if pump is in
dry run condition. See 6016 MIN LOAD CURRENT.
1 = 1 min
0...5 mins
Time
2 mins
6018
DRY RUN RST
TIME
Allows inverter to wait for this time to reset in case of a
dry run fault. After this reset time, inverter starts
automatically.
1 = 1 min
2...300 mins
Time
2 mins
6019
FAULT RESET
TIME
Allows inverter to wait for this time to restart
automatically in case inverter tripped due to under-
voltage fault, PV cell maximum voltage fault or when
actual speed decreased below the minimum motor
speed defined in
1 = 1 min
2...20 mins
Time
2 mins
All parameters
No.
Name/
Value
Description
Def/ FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives Supplement ACS355 Solar pump inverter N827...
Page 4: ......
Page 10: ...10 Safety...
Page 14: ...14 Introduction...
Page 18: ...18 Operating principle and hardware description...
Page 30: ...30 Start up and controls...
Page 36: ...36 Program features...
Page 66: ...66 Actual signals and parameters...
Page 70: ...70 Fault tracing...
Page 76: ...76 Technical data...