Technical data
295
Power cables: terminal sizes, maximum cable diameters and tightening
torques
Dimensions, weights and noise
Symbols
Frame
size
Max cable
diameter for NEMA 1
U1, V1, W1, U2, V2, W2, BRK+ and
BRK-
PE
U1, V1, W1,
U2, V2, W2
BRK+ and
BRK-
Terminal size
Tightening
torque
Clamp size
Tightening
torque
mm
in.
mm
in.
mm
2
AWG
N·m
lbf in. mm
2
AWG
N·m
lbf in.
R0
16
0.63
16
0.63
4.0/6.0
10
0.8
7
25
3
1.2
11
R1
16
0.63
16
0.63
4.0/6.0
10
0.8
7
25
3
1.2
11
R2
16
0.63
16
0.63
4.0/6.0
10
0.8
7
25
3
1.2
11
R3
29
1.14
16
0.63
10.0/16.0
6
1.7
15
25
3
1.2
11
R4
35
1.38
29
1.14
25.0/35.0
2
2.5
22
25
3
1.2
11
00353783.xls G
Frame
size
Dimensions and weights
Noise
IP20 (cabinet) / UL open
H1
H2
H3
W
D
Weight
Noise level
mm
in.
mm
in.
mm
in.
mm
in.
mm
in.
kg
lb
dBA
R0
169
6.65
202
7.95
239
9.41
70
2.76
161
6.34
1.2
2.6
<30
R1
169
6.65
202
7.95
239
9.41
70
2.76
161
6.34
1.2
2.6
50…62
R2
169
6.65
202
7.95
239
9.41
105
4.13
165
6.50
1.5
3.3
50…62
R3
169
6.65
202
7.95
236
9.29
169
6.65
169
6.65
2.5
5.5
50…62
R4
181
7.13
202
7.95
244
9.61
260
10.24
169
6.65
4.4
9.7
<62
00353783.xls G
Frame
size
Dimensions and weights
Noise
IP20 / NEMA 1
H4
H5
W
D
Weight
Noise level
mm
in.
mm
in.
mm
in.
mm
in.
kg
lb
dBA
R0
257
10.12
280
11.02
70
2.76
169
6.65
1.6
3.5
<30
R1
257
10.12
280
11.02
70
2.76
169
6.65
1.6
3.5
50…62
R2
257
10.12
282
11.10
105
4.13
169
6.65
1.9
4.2
50…62
R3
260
10.24
299
11.77
169
6.65
177
6.97
3.1
6.8
50…62
R4
270
10.63
320
12.60
260
10.24
177
6.97
5.0
11.0
<62
00353783.xls G
IP20 (cabinet) / UL open
H1
height without fastenings and clamping plate
H2
height with fastenings, without clamping plate
H3
height with fastenings and clamping plate
IP20 / NEMA 1
H4
height with fastenings and connection box
H5
height with fastenings, connection box and hood
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......