254 Actual signals and parameters
4414 DI STATUS
OUTLET
Selects the digital input for connection of a pressure switch
at the pump/fan outlet. The “normal” state is 1 (active). If the
selected input switches to 0 (inactive), the action defined by
is taken after a delay
expires.
NOT SEL
No digital input selected.
0
DI1
Pump/fan outlet pressure monitored through digital input
DI1
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
4415 OUTLET CTRL
DLY
Sets the delay after which the action defined by parameter
is taken on detection of high
outlet pressure.
60.0 s
0.0…1800.0 s
Delay time
1 = 0.1 s
4416 OUTLET
FORCED REF
This reference is used after detection of high outlet
WARNING!
Make sure that it is safe to continue
operation using this reference.
0.0%
-100.0…
100.0%
Forced reference
1 = 0.1%
4417 PID OUT DEC
TIME
PI controller ramp-down time. See selections
and
for
60.0 s
0.0…1800.0 s
Delay time
1 = 0.1 s
4418 APPL
PROFILE CTL
Parameters
to
provide the Application profile protection
feature, based on long-term monitoring of an internal status
signal. If the selected signal exceeds (and remains above)
the supervision limit for a longer time than the set delay
), the internal status
signal “PROFILE HIGH” is set to 1. The signal can be
directed to a relay output (see parameter group
NOT SEL
Not selected
0
CONTROL
DEV1
is monitored and compared to
. Monitoring the
deviation between the reference and the actual value gives
an indication of the general condition of the pump, piping
and valves.
1
CONTROL
DEV2
is monitored and compared to
. Monitoring the
deviation between the reference and the actual value gives
an indication of the general condition of the pump, piping
and valves.
2
is monitored and
compared to parameter
. The
signal constantly remaining at 100% may indicate a leak in
the output piping.
3
All parameters
No.
Name/Value
Description
Def/FbEq