252 Actual signals and parameters
STOP
Detection of very low inlet pressure stops the drive. The
drive starts again if the pressure exceeds the supervision
level.
1
FAULT
Detection of very low inlet pressure trips the drive on a fault. 2
4405 AI IN VERY
LOW
Supervision level for the secondary inlet pressure
monitoring function. See parameter
0.00%
0.00…100.00% Supervision level
1 = 0.01%
4406 DI STATUS
INLET
Selects the digital input for connection of a pressure switch
at the pump/fan inlet. The “normal” state is 1 (active). If the
selected input switches to 0 (inactive), the action defined by
is executed after the
expires.
NOT SEL
No digital input selected
0
DI1
Pump/fan inlet pressure monitored through digital input DI1 1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
4407 INLET CTRL
DLY
Sets the delay after which the action defined by parameter
is taken on detection of low inlet
pressure
60.0 s
0.0…1800.0 s
Delay time
1 = 0.1 s
4408 INLET
FORCED REF
This reference is used after detection of low inlet pressure.
WARNING!
Make sure that it is safe to continue
operation using this reference.
0.0%
-100.0…
100.0%
Forced reference
1 = 0.1%
4409 OUTLET PROT
CTRL
Enables, and selects the mode of, the primary supervision
of pump/fan outlet pressure.
Note:
Outlet protection is active only when the active
reference is PID.
NOT SEL
Primary outlet pressure supervision not used
0
ALARM
Detection of high outlet pressure produces an alarm on the
control panel display.
1
All parameters
No.
Name/Value
Description
Def/FbEq