Program features 141
Settings
Diagnostics
Example
In the following example, four drives are set up for a duty/assist cycle with internal
setpoints (parameters
,
and
). As shown in the table below, at
each setpoint, a different drive has the highest setpoint value, the second highest
value, and so on, enabling a duty cycle between the four drives.
When the drive system is powered up and the pressure is below all setpoint values,
each drive keeps running until it reaches its setpoint. The drive with the highest
setpoint value keeps running even after this point and becomes the duty drive which
maintains the pressure at the desired value. The drive remains the duty drive until a
setpoint change occurs. Using a timer and a digital inputs as the source for setpoint
selection, setpoints can automatically be rotated, for example, once per day.
If the pressure in the system falls below the second highest setpoint value, that drive
assists to increase the pressure.
To enable the internal setpoints, set
to INTERNAL.
Parameter
Additional information
Local control mode reference type selection
selection
PID1 activation
REF2 minimum limit
PID2 output (external controller) connection to AO
PID control macro selection
Groups
PID1 settings
Group
PID2 settings
Actual signal
Additional information
/
PID 1/2 output value
/
PID 1/2 setpoint value
/
PID 1/2 feedback value
/
PID 1/2 deviation
Drive number Setpoint 1
Setpoint 2
)
Setpoint 3
Setpoint 4
1 50%
40%
35%
30%
2
40%
35%
30%
50%
3
35%
30%
50%
40%
4
30%
50%
40%
35%