Actual signals and parameters in the short view 33
LOAD FD SET
FlashDrop parameter values as defined by the FlashDrop
file. Parameter view is selected by parameter
1611
PARAMETER VIEW
.
FlashDrop is an optional device for fast copying of
parameters to unpowered drives. FlashDrop allows easy
customization of the parameter list, eg selected parameters
can be hidden. For more information, see
MFDT-01
FlashDrop Users Manual
(3AFE68591074 [English]).
31
USER S1
LOAD
User 1 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
0
USER S1
SAVE
Save User 1 macro. Stores the current parameter settings
and the motor model.
-1
USER S2
LOAD
User 2 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
-2
USER S2
SAVE
Save User 2 macro. Stores the current parameter settings
and the motor model.
-3
9905 MOTOR NOM
VOLT
Defines the nominal motor voltage. Must be equal to the
value on the motor rating plate. The drive cannot supply the
motor with a voltage greater than the input power voltage.
Note that the output voltage is not limited by the nominal
motor voltage but increased linearly up to the value of the
input voltage.
WARNING!
Never connect a motor to a drive which
is connected to power line with voltage level higher
than the rated motor voltage.
200 V
units:
230 V
400 V
E units:
400 V
400 V
U units:
460 V
200 V units:
115
345 V
400 V E units:
200
600 V
400 V U units:
230
690 V
Voltage.
Note:
The stress on the motor insulations is always
dependent on the drive supply voltage. This also applies to
the case where the motor voltage rating is lower than the
rating of the drive and the supply of the drive.
1 = 1 V
9906 MOTOR NOM
CURR
Defines the nominal motor current. Must be equal to the
value on the motor rating plate.
I
2N
0.2 2.0 ·
I
2N
Current
1 = 0.1 A
9907 MOTOR NOM
FREQ
Defines the nominal motor frequency, ie the frequency at
which the output voltage equals the motor nominal voltage:
Field weakening point = Nom. frequency · Supply voltage /
Motor nom. voltage
E: 50.0 Hz
U: 60.0 Hz
10.0 500.0 Hz Frequency
1 = 0.1 Hz
Parameters in the short parameter view
No.
Name/Value
Description
Def/FbEq
Output voltage
Output frequency
Input voltage
9907
9905