Actual signals and parameters in the short view 29
Actual signals in the short parameter view
Parameters in the short parameter view
Actual signals in the short parameter view
No.
Name/Value
Description
FbEq
04 FAULT HISTORY
Fault history (read-only)
0401 LAST FAULT
Code of the latest fault. See chapter
Fault tracing
in
ACS310
Users Manual
(3AUA0000044201 [English]) for the codes.
0 = Fault history is clear (on panel display = NO RECORD).
1 = 1
Parameters in the short parameter view
No.
Name/Value
Description
Def/FbEq
11 REFERENCE
SELECT
Panel reference type, external control location selection and
external reference sources and limits
1105 REF1 MAX
Defines the maximum value for external reference REF1.
Corresponds to the maximum setting of the used source
signal.
E: 50.0 Hz
U: 60.0 Hz
0.0 500.0 Hz
Maximum value in Hz. See the example for parameter 1104
REF1 MIN in
ACS310 Users Manual
(3AUA0000044201
[English]).
1 = 0.1 Hz
12 CONSTANT
SPEEDS
Constant speed (drive output frequency) selection and
values. By default constant speed selection is made through
digital inputs DI3 and DI4.1 = DI active, 0 = DI inactive.
For more information, see chapter
Program features
,
section
Constant speeds
in
ACS310 Users Manual
(3AUA0000044201 [English]).
1202 CONST
SPEED 1
Defines constant drive output frequency 1.
E: 5.0 Hz
U: 6.0 Hz
0.0 500.0 Hz
Output frequency in Hz.
1 = 0.1 Hz
1203 CONST
SPEED 2
Defines constant drive output frequency 2.
E: 10.0 Hz
U: 12.0 Hz
0.0 500.0 Hz
Output frequency in Hz.
1 = 0.1 Hz
1204 CONST
SPEED 3
Defines constant drive output frequency 3.
E: 15.0 Hz
U: 18.0 Hz
0.0 500.0 Hz
Output frequency in Hz.
1 = 0.1 Hz
DI3 DI4 Operation
0
0 No constant speed
1
0 Speed defined by parameter
1202
CONST SPEED 1
0
1 Speed defined by parameter
1203
CONST SPEED 2
1
1 Speed defined by parameter
1204
CONST SPEED 3