154 Parameters
Selects the source of motor potentiometer up signal.
0 = No change
1 = Increase motor potentiometer value. (If both the
up and down sources are on, the potentiometer value
will not change.)
not used
Not used
0.
0
Used
1.
1
DI1
Digital input DI1 (
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
Supervision 1
.
24
Supervision 2
Bit 1 of
.
25
Supervision 3
.
26
Supervision 4
.
27
Supervision 5
28
Supervision 6
Bit 5 of
29
Source selection (see
).
-
Selects the source of motor potentiometer down
signal.
0 = No change
1 = Decrease motor potentiometer value. (If both the
up and down sources are on, the potentiometer value
will not change.)
For the selections, see parameter
not used
Defines the change rate of the motor potentiometer.
This parameter specifies the time required for the
motor potentiometer to change from minimum
(parameter
) to maximum (parameter
). The
same change rate applies in both directions.
40.0 s
0.0…3600.0 s
Motor potentiometer change time.
1 = 1 s
Defines the minimum value of the motor
potentiometer.
Note:
If vector control mode is used, the value of this
parameter must be changed.
-50.00
-32768.00… 32767.00
Motor potentiometer minimum.
1 = 1
Defines the maximum value of the motor
potentiometer.
Note:
If vector control mode is used, the value of this
parameter must be changed.
50.00
-32768.00… 32767.00
Motor potentiometer maximum.
1 = 1
Shows the output of the motor potentiometer
function. (The motor potentiometer is configured
using parameters
…
.)
This parameter is read-only.
-
-32768.00… 32767.00
Value of motor potentiometer.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280