ACS2000 User manual
2UEA001270 Rev. F
2-9 (28)
Chapter 2 - Power electronics and cabinet features
Stand-by mode
Once the DC link is charged, it is possible to keep the drive in this state to
facilitate a more rapid start-up procedure. The losses during stand-by
mode are approximately 1% of the nominal power and are caused from
small losses from the AFE, the INU and the auxiliaries.
2.2.4.2 Grounding switch
The grounding switch is a safety device that enables safe access to the
AFE / INU compartment of the drive.
Figure 2-7
Grounding switch
When the switch is in the grounded position, the input filter, AFE, DC link,
INU and dV/dt output filter of the drive are connected to the PE (protective
earth) ground, provided none of the phase modules is extracted from the
cabinet. Refer to Figure 2-8.
Legend
1
Grounding switch handle
(Shown in grounded position)
2
Grounding switch - detailed
interior view
Frame 1
Typical Frames 2, 3 (Frame 2 pictured)
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......