Chapter 6 - Electrical installation
6.5
Ground cable and cable shield connections
The terminal entry unit is equipped with a ground bus to ground the cable
armor and shield connections of the line and motor cables. Attach one lug
per terminal.
Figure 6-4
Ground bus
Terminal details
•
Busbar dimensions: 75 mm [3 in] wide x 3.18 mm [0.125 in] thick
•
Hole diameters:
7 mm [0.28 in] for wire connections
13 mm [0.5 in] for fastening bolt
Legend
1
PE ground bus