10.6.4 Grounding switch is not released
When the DC link of the drive has been discharged,
the lamp GROUNDING SWITCH UNLOCKED
lights
up to indicate that the grounding switch is
released and can be turned to the grounded posi-
tion.
If the lamp does not light up, proceed as fol-
lows:
1. Do not force the grounding switch in any direc-
tion.
2. To test the lamp GROUNDING SWITCH
UNLOCKED, activate the lamp test with param-
eter 16.7.
(For information on setting parameters, see
- If the lamp does not light up, replace it.
- If the lamp lights up after it was replaced,
continue with step
.
- If the lamp does not light up after it was
replaced, continue with step
.
3. Verify that the MCB (main circuit breaker) is
open.
a. If the MCB is open, check that it is locked
out.
b. Check if the SUPPLY OFF lamp is lit.
If the lamp is lit, the feedback signal “main
circuit breaker open” is present at digital
input DI09 of I/O module A3411.
4. Check if the LED of digital output DO03 (I/O
module A3401) is lit.
If the LED is lit, the grounding switch is
released.
5. Check the discharging level of the DC link.
If the value of parameter 2.01 DC VOLTAGE is
below 50 V, the DC link is discharged.
If the DC link is discharged, the message
ReadyOn
is displayed on the CDP control panel.
6. Verify that hazardous voltages from the motor
cannot be fed into the drive.
7. Carefully turn the grounding switch to the
grounded position f it has been verified:
- that hazardous voltages cannot be fed into
the drive from the main power supply or the
motor,
- that the DC link is discharged,
- that the grounding switch is released (DO03
is energized).
- that the drive status is
ReadyOn
.
If you cannot turn the grounding switch, con-
tinue with
8. Switch off and lockout all auxiliary voltages
from external sources.
9. Verify that the drive system is de-energized.
10. Ground the drive with a grounding set (option).
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
Summary of Contents for ACS2000 AFE 1MVA
Page 6: ...170 Replacing filter mats 171 Phase modules location 171 Phase module Dimensions and weight ...
Page 8: ...Terms trademarks related documentation ...
Page 13: ...13 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 14: ...General information on manual and drive ...
Page 19: ...19 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 20: ...Important note on main circuit breaker ...
Page 48: ...Chapter 3 Control system 49 Overview 50 Main components 54 I O interfaces ...
Page 67: ...67 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 77: ...77 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 83: ...83 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J 5 1 3 2 1 4 A B C E D ...
Page 85: ...85 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 113: ...113 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 114: ...Commissioning check list ...
Page 149: ...149 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV J ...
Page 176: ......