246 Parameters
PID output
PID controller output.
2
Selects the source that determines whether process PID
parameter set 1 (parameters
…
) or set 2
(group
) is used.
0 = PID set 1 in use
1 = PID set 2 in use
PID set 1
PID set 1.
0
PID set 2
PID set 2.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
Supervision 1
Bit 0 of
21
Supervision 2
Bit 1 of
22
Supervision 3
Bit 2 of
23
-
Prevention of PID integration term increase for PID set 1.
No
Increase prevention not in use.
0
Limiting
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is
valid for the PID set 1.
1
Ext PID min lim
The process PID integration term is not increased when
the output of the external PID has reached it's minimum
limit. In this setup, the external PID is used as a source for
the process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not increased when
the output of the external PID has reached it's maximum
limit. In this setup, the external PID is used as a source for
the process PID. This parameter is valid for the PID set 1.
3
Prevention of PID integration term decrease for PID set 1.
No
Decrease prevention not in use.
0
Limiting
The PID integration term is not decreased if the minimum
value for the PID output is reached. This parameter is
valid for the PID set 1.
1
Ext PID min lim
The process PID integration term is not decreased when
the output of the external PID has reached it's minimum
limit. In this setup, the external PID is used as a source for
the process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not decreased when
the output of the external PID has reached it's maximum
limit. In this setup, the external PID is used as a source for
the process PID. This parameter is valid for the PID set 1.
3
Selects the source of process PID set 1 activation.
Off
Set 1 PID activation source is Off.
0
No.
Name/Value
Description
Default
FbEq 16