210 Parameters
Warning/Warning
3
Event/Event
4
No Indication/No
Indication
5
Selects how the drive reacts to incorrect input power and
motor cable connection (ie. input power cable is
connected to drive motor connection).
No action
No action taken.
0
Fault
The drive trips on fault
.
1
Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
• The drive exceeds the stall current limit (
)
, and
• the output frequency is below the level set by
parameter
or the motor
speed is below the level set by parameter
, and
• the conditions above have been true longer than the
time set by parameter
No action
None (stall supervision disabled).
0
Warning
warning.
1
Fault
The drive trips on fault
2
Stall current limit in percent of the nominal current of the
motor. See parameter
200.0%
0.0…1600.0%
Stall current limit.
-
No.
Name/Value
Description
Default
FbEq 16
Inputs
Indication (running or stopped)
IN1
IN2
0
0
Warning
0
1
1
0
1
1
(Normal operation)
Inputs
Indication (running or stopped)
IN1
IN2
0
0
Event
0
1
and fault
1
0
and fault
1
1
(Normal operation)
Inputs
Indication (running or stopped)
IN1
IN2
0
0
None
0
1
1
0
1
1
(Normal operation)