Fault tracing 349
9083
External fault 3
(Editable message text)
Programmable fault:
Fault in external device 3.
Check the external device.
Check setting of parameter
9084
External fault 4
(Editable message text)
Programmable fault:
Fault in external device 5.
Check the external device.
Check setting of parameter
9085
External fault 5
(Editable message text)
Programmable fault:
Fault in external device 5.
Check the external device.
Check setting of parameter
FA81
Safe torque off 1
Safe torque off function is
active, ie. STO circuit 1 is
broken.
Check safety circuit connections. For
more information, see chapter
The Safe
torque off function
in the hardware
manual of the drive and description of
parameter
(page
).
FA82
Safe torque off 2
Safe torque off function is
active, ie. STO circuit 2 is
broken.
FF61
ID run
Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not locked.
0001 Maximum current limit too low.
Check settings of parameters
. Make sure that
>
.
Check that the drive is dimensioned
correctly according to the motor.
0002 Maximum speed limit or
calculated field weakening
point too low.
Check settings of parameters
•
•
•
•
•
Make sure that
•
> (0.55 ×
(0.50 × synchronous speed)
•
< 0, and
• supply voltage > (0.66 ×
Code
(hex)
Fault / Aux. code
Cause
What to do