Parameters 293
Defines the nominal motor frequency. This setting must
match the value on the rating plate of the motor.
Note:
This parameter cannot be changed while the drive
is running.
50.00 Hz
0.00…500.00 Hz
Nominal frequency of the motor.
10 = 1 Hz
Defines the nominal motor speed. The setting must match
the value on the rating plate of the motor.
Note:
This parameter cannot be changed while the drive
is running.
1435 rpm
0…30000 rpm
Nominal speed of the motor.
1 = 1 rpm
Defines the nominal motor power. The setting must match
the value on the rating plate of the motor. If multiple
motors are connected to the drive, enter the total power of
the motors. The unit is selected by parameter
Note:
This parameter cannot be changed while the drive
is running.
1.10 kW or
hp
0.00… 10000.00 kW
or 0.00… 13404.83 hp
Nominal power of the motor.
1 = 0.01 unit
(see par.
)
Defines the cosphi of the motor for a more accurate motor
model. This value is not obligatory, but is useful with an
asynchronous motor, especially when performing a
standstill identification run. With a permanent magnet or
synchronous reluctance motor, this value is not needed.
Notes:
• Do not enter an estimated value. If you do not know the
• exact value, leave the parameter at zero.
• This parameter cannot be changed while the drive is
running.
0.00
0.00…1.00
Cosphi of the motor.
100 = 1
Defines the nominal motor shaft torque for a more
accurate motor model. Not obligatory. The unit is selected
by parameter
Note:
This parameter cannot be changed while the drive
is running.
0.000
N·m or lb·ft
0.000…4000000.000
N·m or
0.000…2950248.597
lb·ft
Nominal motor torque.
1 = 100 unit
No.
Name/Value
Description
Default