11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
169/174
11.6.10 Inspecting and replacing batteries
Figure 11-6: Control compartment – battery location
11.6.10.1 Checking and replacement indications
The end of the battery life is indicated as follows:
- CDP control panel displays an alarm message.
- Alarm LED on the power supply unit for the battery lights up (3 in Fig. 11-6).
When the end of the battery life is indicated, the drive continues to operate until the time set
with parameter
145.26 Batt-Alm.Tim-out
has elapsed.
ABB recommends replacing all of the batteries when one battery is at end of life.
(1) Power supply unit for battery pack 1
(2) Alarm LED
(3) Battery pack 1
1
2
3