Actual signals and parameters
217
95.06
LCU Q PW REF
Defines the reference value for the line-side converter reactive power
generation. Line-side converter can generate reactive power to the supply
network. This reference is written into line-side converter unit parameter
Q POWER REF2. For more information, see
IGBT Supply Control Program 7.x
Firmware manual
[3AFE68315735 (English)].
Example 1:
When parameter 24.03 Q POWER REF2 SEL is set to PERCENT,
value 10000 of parameter 24.02 Q POWER REF2 equals to value 100% of
parameter 24.01 Q POWER REF (that is 100% of the converter nominal power
given in signal 04.06 CONV NOM POWER).
Example 2:
When parameter 24.03 Q POWER REF2 SEL is set to kVAr, value
1000 of parameter 24.02 Q POWER REF2 equals to parameter 24.01 Q
POWER REF value calculated with the following equation: 100 · (1000 kVAr
divided by converter nominal power in kVAr)%.
Example 3:
When parameter 24.03 Q POWER REF2 SEL is set to PHI, value
3000 of parameter 24.02 POWER REF2 equals approximately to parameter
24.01 Q POWER REF value calculated with the following equation:
Parameter 24.03 values are converter to degrees by the line-side converter
application program: -3000 ... 30000 -30°... 30°. Value -10000/10000 equals
to -30° / 30°, since the range is limited to -3000/3000.
-10000...10000
Reference value.
See par.
description.
95.07
LCU DC REF
Defines the intermediate circuit DC voltage reference for the line-side
converter. This reference is written into line-side converter parameter 23.01 DC
VOLT REF. For more information,
see IGBT Supply Control Program 7.x
Firmware manual
[3AFE68315735 (English)].
0...1100 V
Voltage
1 = 1 V
95.08
LCU PAR1 SEL
Selects the line-side converter address from which the actual signal
LCU
ACT SIGNAL1 is read from.
0…9999
Line-side converter parameter index. For more information, see
IGBT Supply
Control Program 7.x Firmware manual
[3AFE68315735 (English)].
0…9999
95.09
LCU PAR2 SEL
Selects the line-side converter address from which the actual signal
LCU
ACT SIGNAL2 is read from.
0…9999
Line-side converter parameter index. For more information, see
IGBT Supply
Control Program 7.x Firmware manual
[3AFE68315735 (English)].
0…9999
95.10
TEMP INV AMBIENT
Defines the ambient temperature for the Enhanced drive temperature
monitoring function.
Note:
If ambient temperature exceeds 40 °C, the drive load capacity
decreases. See the derating instructions in the appropriate hardware manual.
20...50°C
Temperature
10 = 1 °C
Index
Name/Selection
Description
FbEq
30
(
)
cos
P
S
----
P
P
2
Q
2
+
------------------------
=
=
S
Q
P
Positive reference 30° denotes capacitive load.
Negative reference 30° denotes inductive load.
30
°
P = signal 01.09 POWER value
=
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...