Appendix A – ACS/ACC 600 Technical Data
A-12
601/604/607 US Supplement
Heat DIssipation
Requirements
ACx 601/4/7 drives are self-cooled. The table below gives the heat
dissipated into the hot air exhausted from the drives. If the drives are
installed in a confined space, the heat must be removed from the area
by ventilation or air conditioning equipment.
ACx 600 Type Code
Heat Dissipation
Watts
BTU/Hr
ACx 601-0003-2
112
380
ACx 601-0005-2
156
530
ACx 601-0006-2
182
620
ACx 601-0009-2
217
740
ACx 601-0011-2
370
1265
ACx 601-0016-2
540
1840
ACx 601-0020-2
620
2120
ACx 601-0025-2
1000
3400
ACx 601-0030-2
1120
3800
ACx 601-0040-2
1480
5100
ACx 601-0050-2
1880
6400
ACx 601-0060-2
2185
7500
ACx 601-0070-2
2950
10100
ACx 601-0080-2
3200
10900
ACx 601-0100-2
4300
14700
ACx 604/7-0120-2
6300
21500
ACx 604/7-0140-2
7800
26600
ACx 604/7-0170-2
9600
32800
ACx 601-0006-4
100
341
ACx 601-0009-4
130
444
ACx 601-0011-4
170
581
ACx 601-0016-4
240
820
ACx 601-0020-4
320
1093
ACx 601-0025-4
460
1571
ACx 601-0030-4
620
2117
ACx 601-0040-4
760
2596
ACx 601-0050-4
920
3142
ACx 601-0060-4
1130
3859
ACx 601-0070-4
1530
5225
ACx 601-0100-4
1840
6284
ACx 601-0120-4
2250
7684
ACx 601-0140-4
2700
9221
ACx 604/7-0120-4
2300
7848
ACx 604/7-0140-4
2800
9551
ACx 604/7-0170-4
3300
11260
ACx 604/7-0210-4
4000
13650
ACx 604/7-0260-4
5000
17061
ACx 604/7-0320-4
6300
21500
ACx 604/7-0400-4
7900
26956
ACx 604/7-0490-5
10000
34121
ACx 604/7-0610-5
12500
42652
ACx 604/7-0760-5
12500
53912