du/dt Filters Installation Guide
5
du/dt Filters Installation Guide
Contents
This document contains the following information:
• General notes and restrictions
• Technical data (including allowable ambient conditions)
• Internal circuit diagrams
• Power connection diagrams
• Filter selection tables
• Dimensional drawings (including terminal sizes and tightening torques).
General notes and restrictions
Observe the following before you start to install the du/dt filters:
WARNING!
Do not attempt any work on a powered drive. After switching off the
mains, always allow the intermediate circuit capacitors 5 minutes to discharge before
working on the frequency converter, the motor or the motor cable. It is good practice
to check (with a voltage indicating instrument) that the drive is in fact discharged
before beginning work.
• Unprotected (IP00) filters must be encased to meet the local safety requirements.
• The surface of the IP22/IP54 filter housing can reach a temperature up to 40 °C
higher than the ambient temperature.
• Shielded cable must be used between enclosures.
• Filters must be grounded to the protective earth (PE) by using the fixing holes in
the mounting legs.
•
Maximum drive output frequency:
120 Hz
•
Maximum average switching frequency:
3 kHz (converter units with supply voltage < 500 V) or
2 kHz (converter units with supply voltage > 500 V)
•
Maximum cable length between the drive output and the filter:
3 m
•
Maximum motor cable length
for AOCH0xxx-70 filters:
300 m (cumulative for
several parallel-connected motors)
Summary of Contents for ACS 600 MultiDrive
Page 2: ...3AFE 58933368 REV D EN EFFECTIVE 20 10 2003 2003 ABB Oy All Rights Reserved...
Page 4: ...Table of contents 4...
Page 12: ...du dt Filters Installation Guide 12 NOCH0760 60...
Page 13: ...du dt Filters Installation Guide 13 NOCH0400 60...
Page 14: ...du dt Filters Installation Guide 14 NOCH0400 60...
Page 15: ...du dt Filters Installation Guide 15 AOCH0400 70 AOCH0260 70...
Page 23: ...du dt Filters Installation Guide 23...
Page 24: ...du dt Filters Installation Guide 24 NOCH0760 60 Weight 43 kg 95 lbs 1 1 2 1 1 2 2 2...
Page 25: ...du dt Filters Installation Guide 25...
Page 26: ...du dt Filters Installation Guide 26 64787845 A NOCH0120 62 NOCH0120 65 Weight 45 kg 99 lbs...
Page 27: ......