ACS 160 User’s Manual
121
Figure 33 Cable recommendations and restrictions.
The general rule for cable screen effectiveness is: the better and tighter the screen of the cable, the
lower the radiated emission level. Example of an effective construction is presented in Figure 34.
Figure 34 Effective motor cable screen (e.g. Ölflex-Servo-FD 780 CP, Lappkabel or MCCMK, NK
Cables).
Clamp the cable shield into the gland plate at the converter end and twist the cable screen wires
together into a bundle not longer than five times its width and connect it to the terminal marked
,
if you are using cable without a separate PE conductor.
At the motor end the motor cable screen must be earthed 360 degrees with an EMC cable gland
(e.g. ZEMREX SCG Screened cable glands) or the screen wires must be twisted together into a
bundle not longer than five times its width and connected to the PE terminal of the motor.
Symmetrical shielded cable: three phase
conductors and a concentric or otherwise
symmetrically constructed PE conductor,
and a shield
Recommended
PE
conductor
and shield
Shield
Shield
A separate PE conductor is required if the
conductivity of the cable shield is < 50 %
of the conductivity of the phase conductor.
Not allowed for motor cables.
Shield
PE
PE
PE
Allowed for motor cables
with phase
conductor cross section up to 10 mm
2
.
A four -conductor system: three phase
conductors and a protective conductor.
Allowed
Insulation jacket
Braided metallic screen
Inner insulator
L1
L2
L3
Summary of Contents for ACS 160
Page 2: ......
Page 4: ......
Page 10: ...viii ACS 160 User s Manual ...
Page 12: ...2 ACS 160 User s Manual ...
Page 32: ...22 ACS 160 User s Manual ...
Page 42: ...32 ACS 160 User s Manual ...
Page 56: ...46 ACS 160 User s Manual ...
Page 116: ...106 ACS 160 User s Manual ...
Page 122: ...112 ACS 160 User s Manual ...
Page 126: ...116 ACS 160 User s Manual ...
Page 136: ...126 ACS 160 User s Manual ...
Page 137: ......