Parameters 233
53
53 FBA data out
Selection of data to be transferred from fieldbus controller to
drive via fieldbus adapter.
53.01
FBA data out1
select data to be transferred from
the fieldbus controller to the drive.
1
Control Word (16 bits)
1
2
Reference REF1 (16 bits)
2
3
Reference REF2 (16 bits)
3
11
Control Word (32 bits)
11
12
Reference REF1 (32 bits)
12
13
Reference REF2 (32 bits)
13
101…9999
Parameter index
1 = 1
…
…
…
…
53.12
FBA data out12
See parameter
.
56
56 Panel display
Selection of signals to be displayed on control panel.
56.01
Signal1 param
Selects the first signal to be displayed on the optional control
panel. The default signal is
.
00.00 … 255.255
1st signal to be displayed.
-
56.02
Signal2 param
Selects the second signal to be displayed on the optional
control panel. The default signal is
00.00 … 255.255
2nd signal to be displayed.
-
56.03
Signal3 param
Selects the third signal to be displayed on the optional
control panel. The default signal is
00.00 … 255.255
3rd signal to be displayed.
-
56.04
Signal1 mode
Defines the way the signal selected by parameter
is displayed on the optional control panel.
Disabled
Signal not displayed. Any other signals that are not disabled
are shown together with their respective signal name.
-1
Normal
Shows the signal as a numerical value followed by unit.
0
Bar
Shows the signal as a horizontal bar.
1
Drive name
Shows the drive name. (The drive name can be set using the
DriveStudio PC tool.)
2
Drive type
Shows the drive type.
3
56.05
Signal2 mode
Defines the way the signal selected by parameter
is displayed on the optional control panel.
Disabled
Signal not displayed. Any other signals that are not disabled
are shown together with their respective signal name.
-1
Normal
Shows the signal as a numerical value followed by unit.
0
Bar
Shows the signal as a horizontal bar.
1
Drive name
Shows the drive name. (The drive name can be set using the
DriveStudio PC tool.)
2
Drive type
Shows the drive type.
3
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...