Program features 69
User parameter sets
The drive supports four user parameter sets that can be saved to the
permanent memory and recalled using drive parameters. It is also possible to
use digital inputs to switch between user parameter sets. To change a user
parameter set, make sure the drive is not modulating.
A user parameter set contains all editable values in parameter groups 10…99
except the following:
• forced I/O values such as parameters
and
• I/O extension module settings (group 15)
• fieldbus communication settings (groups 50…53 and 58)
• parameter
.
As the motor settings are included in the user parameter sets, make sure the
settings correspond to the motor used in the application before recalling a user
set. In an application where different motors are used with the drive, perform
the motor ID run with each motor and the save the results in different user sets.
The appropriate set can then be recalled when the motor is switched on.
Settings and diagnostics
Parameters:
…
(page
),
(page
) and
(page
)
Event:
(page
User lock
For better cyber security, it is highly recommended that you set a master pass
code to prevent changing of parameter values and/or the loading of firmware
and other files.
WARNING!
ABB will not be liable for damages or losses caused by the
failure to activate the user lock using a new pass code. See
To activate the user lock for the first time:
• Enter the default pass code, 10000000, into
. This will make
visible.
. Always use eight
digits, if using Drive composer PC tool. Finish with Enter.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...