Program features 55
Motor identification
The performance of vector control is based on an accurate motor model
determined during the motor start-up.
A motor identification magnetization is automatically performed for the first
time when the start command is given. During this first startup, the motor is
magnetized at zero speed for several seconds and the motor and motor cable
resistance are measured to allow the motor model to be created. This
identification method is suitable for most applications.
In some applications a separate identification run (ID run) can be performed.
Settings
(page
).
Scalar motor control
Scalar motor control is the default motor control method. In scalar control
mode, the drive is controlled with a frequency reference.
ABB recommends to activate the scalar motor control mode in the following
situations:
• If the exact nominal motor values are not available or the drive needs to run
different motors after commissioning.
• If a short commissioning time is needed.
• If the application does not require the best possible motor control
performance.
• If the nominal current of the motor is less than 1/6
th
of the nominal output
current of the drive.
• If the drive is used without a motor connected (for example, for test
purposes).
• If the drive runs a medium-voltage motor through a step-up transformer.
• If the drive is equipped with a sine filter.
Note:
Performance of the vector control is not achieved in scalar control.
See also section
).
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...