262 Parameters
98
Motor values supplied by the user that are used
in the motor model.
These parameters are useful for non-standard
motors, or to just get more accurate motor
control of the motor on site. A better motor
model always improves the shaft performance.
Activates the motor model parameters
.
Notes
:
• Parameter value is automatically set to zero
when ID run is selected by parameter
. The values of parameters
…
are then updated according to
the motor characteristics identified during the
ID run.
• Measurements made directly from the motor
terminals during the ID run are likely to
produce slightly different values than those on
a data sheet from a motor manufacturer.
• This parameter cannot be changed while the
drive is running.
Not selected
Parameters
inactive.
0
Motor
parameters
The values of parameters
are used
as the motor model.
1
Defines the stator resistance
R
S
of the motor
model.
With a star-connected motor,
R
S
is the resistance
of one winding. With a delta-connected motor,
R
S
is one-third of the resistance of one winding.
0.00000
p.u.
0.00000…
0.50000 p.u.
Stator resistance in per unit.
-
Defines the rotor resistance
R
R
of the motor
model.
0.00000
p.u.
0.00000…
0.50000 p.u.
Rotor resistance in per unit.
-
Defines the main inductance
L
M
of the motor
model.
0.00000
p.u.
0.00000…
10.00000 p.u.
Main inductance in per unit.
-
Defines the leakage inductance
σ
L
S
.
0.00000
p.u.
0.00000…
1.00000 p.u.
Leakage inductance in per unit.
-
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...