220 Parameters
Fault
The drive monitors communication loss when
start/stop is expected from the EFB on the
currently active control location. Drive trips on
if control in the currently
active control location is expected from the EFB
or reference is coming from the EFB, and the
communication is lost.
1
Fault always
Drive continuously monitors for communication
loss. Drive trips on
. This
happens even thought the drive is in a control
location where the EFB start/stop or reference is
not used.
4
Warning
Drive generates an
warning.
This occurs even though no control is expected
from the EFB.
WARNING!
Make sure that it is safe to
continue operation in case of a
communication break.
5
Defines which message types reset the timeout
counter for detecting an EFB communication
loss.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
).
See also parameters
and
.
Any message
Any message addressed to the drive resets the
timeout.
1
Cw / Ref1 / Ref2 A write of the control word or a reference resets
the timeout.
2
Sets a timeout for EFB communication. If a
communication break lasts longer than the
timeout, the action specified by parameter
is taken.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
See also parameter
.
60.0 s
0.0…6000.0 s
EFB communication timeout.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...