Parameters 219
Shows a count of valid packets addressed to the
drive. During normal operation, this number
increases constantly.
Can be reset from the control panel by keeping
Reset down for over 3 seconds.
-
0…4294967295 Number of received packets addressed to the
drive.
1 = 1
Shows a count of valid packets transmitted by
the drive. During normal operation, this number
increases constantly.
Can be reset from the control panel by keeping
Reset down for over 3 seconds.
-
0…4294967295 Number of transmitted packets.
1 = 1
Shows a count of valid packets addressed to any
device on the bus. During normal operation, this
number increases constantly.
Can be reset from the control panel by keeping
Reset down for over 3 seconds.
-
0…4294967295 Number of all received packets.
1 = 1
Shows a count of character errors received by the
drive. An increasing count indicates a
configuration problem on the bus.
Can be reset from the control panel by keeping
Reset down for over 3 seconds.
-
0…4294967295 Number of UART errors.
1 = 1
Shows a count of packets with a CRC error
received by the drive. An increasing count
indicates interference on the bus.
Can be reset from the control panel by keeping
Reset down for over 3 seconds.
-
0…4294967295 Number of CRC errors.
1 = 1
Selects how the drive reacts to an EFB
communication break.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
No action
No action taken (monitoring disabled).
0
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...