Parameters 93
Defines the real maximum value of the signal (selected by
parameter
) that corresponds to the
maximum required AO2 output value (defined by parameter
). See parameter
. See parameter
about the
AO automatic scaling.
3.2 A
-32768.0…32767.0
Real signal value corresponding to maximum AO2 output
value.
1 = 1
Defines the minimum output value for analog output AO2.
See also drawing at parameter
.
0.000 mA
0.000 … 22.000 mA Minimum AO2 output value.
1000 = 1 mA
Defines the maximum output value for analog output AO2.
See also drawing at parameter
.
20.000 mA
0.000 … 22.000 mA Maximum AO2 output value.
1000 = 1 mA
Storage parameter for controlling analog output AO1 eg.
through the embedded fieldbus interface.
In parameter
.
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(
) to
0.00
-327.68…327.67
Storage parameter for AO1.
100 = 1
Storage parameter for controlling analog output AO2 eg.
through the embedded fieldbus interface.
In parameter
.
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(
) to
0.00
-327.68…327.67
Storage parameter for AO2.
100 = 1
21
Start and stop modes.
Selects the motor start function for the vector motor control
mode, ie. when
is set to
Notes
:
• The start function for the scalar motor control mode is
• Starting into a rotating motor is not possible when DC
magnetizing is selected (
• With permanent magnet motors,
start mode
must be used.
• This parameter cannot be changed while the drive is
running.
Fast
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is determined automatically, being typically
200 ms to 2 s depending on motor size. This mode should be
selected if a high break-away torque is required.
0
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 93 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...