Parameters 103
Shows torque controller limitation status word.
This parameter is read-only.
0b0000
0b0000…0b1111
Torque limitation status word.
1 = 1
Defines the drive current limit monitor time after which action
is taken as specified in the parameter
10.00
0.00...120.00s
Current limit monitor time.
100=1
Selects how the drive reacts when the drive reaches the
current limit (
) and exceeds the
monitor time set by parameter
.
No action
None (current limit action disabled).
0
Warning
The drive generates an
1
Fault
The drive trips on fault
2
Defines the minimum allowed speed.
WARNING!
This value must not be higher than
.
WARNING!
In speed control mode only. In frequency
control mode, use frequency limits (
).
-3000.00 rpm
-30000.00…
30000.00 rpm
Minimum allowed speed.
1 = 1
Defines the maximum allowed speed.
WARNING!
This value must not be lower than
.
WARNING!
In speed control mode only. In frequency
control mode, use frequency limits (
).
3000.00 rpm
-30000.00…
30000.00 rpm
Maximum speed.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Undervoltage
*1 = Intermediate DC circuit undervoltage
1
Overvoltage
*1 = Intermediate DC circuit overvoltage
2
Minimum torque *1 = Torque is being limited by
3
Maximum torque *1 = Torque is being limited by
4
Internal current
1 = An inverter current limit (identified by bits 8…11) is active
5
Load angle
(With permanent magnet motors and reluctance motors only)
1 = Load angle limit is active, ie. the motor cannot produce any more
torque
6
Motor pullout
(With asynchronous motors only)
Motor pull-out limit is active, ie. the motor cannot produce any more
torque
7
Reserved
8
Thermal
1 = Input current is being limited by the main circuit thermal limit
9
Max current
*1 = Maximum output current (
I
MAX
) is being limited
10
User current
*1 = Output current is being limited by
11
Thermal IGBT
*1 = Output current is being limited by a calculated thermal current
value
12…15 Reserved
*Only one out of bits 0…3, and one out of bits 9…11 can be on simultaneously. The bit typically
indicates the limit that is exceeded first.
ACQ80 FW.book Page 103 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...