Fault tracing 359
9084
External fault 4
(Editable message text)
Programmable fault:
Fault in external device 4.
Check the external device.
Check setting of parameter
9085
External fault 5
(Editable message text)
Programmable fault:
Fault in external device 5.
Check the external device.
Check setting of parameter
FA81
Safe torque off 1
Safe torque off function is
active, ie. STO circuit 1 is
broken.
Check safety circuit connections. For
more information, see chapter
The
Safe torque off function
in the
Hardware manual
of the drive and
(page
Check the value of parameter
.
FA82
Safe torque off 2
Safe torque off function is
active, ie. STO circuit 2 is
broken.
FF61
ID run
Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group
Check that no external control system
is connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not
locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
0001 Maximum current limit too low.
Check settings of parameters
and
. Make sure that
>
Check that the drive is dimensioned
correctly according to the motor.
0002 Maximum speed limit or
calculated field weakening
point too low.
Check settings of parameters
•
•
•
•
•
.
Make sure that
•
> (0.55 ×
(0.50 × synchronous speed)
•
< 0, and
).
Code
(hex)
Fault / Aux. code
Cause
What to do
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...