176 Parameters
Defines the minimum allowed frequency.
WARNING!
This value must not be higher than
WARNING!
in frequency control mode only.
0.00 Hz
-500.00…500.00
Hz
Minimum frequency.
See par.
Defines the maximum allowed frequency.
Note:
This parameter does not affect the frequency
acceleration and deceleration ramp times. See parameter
WARNING!
This value must not be lower than
.
WARNING!
in frequency control mode only.
50.00 Hz;
60.00 Hz
(
-500.00…500.00
Hz
Maximum frequency.
See par.
Defines the maximum allowed motor current. This depends
on the drive type; it is automatically determined on the basis
of the rating.
0.00 A
0.00…30000.00 A
Maximum motor current.
1 = 1 A
Defines a minimum torque limit for the drive (in percent of
nominal motor torque).
Note:
If your application, like a pump or a fan, requires that
the motor must rotate in one direction only, use speed/
frequency limit (
) to achieve this. Do not set parameter
to 0%, as
the drive is then not able to stop correctly.
WARNING!
In torque control mode (vector motor
control) only.
-300.0%
-1600.0…0.0%
Minimum torque limit 1.
See par.
Defines a maximum torque limit for the drive (in percent of
nominal motor torque).
WARNING!
In torque control mode (vector motor
control) only.
300.0%
0.0…1600.0%
Maximum torque 1.
See par.
Defines the maximum allowed power fed by the inverter to the
motor in percent of nominal motor power.
300.00%
0.00…600.00%
Maximum motoring power.
1 = 1%
Defines the maximum allowed power fed by the motor to the
inverter in percent of nominal motor power.
Note:
If your application, like a pump or a fan, requires that
the motor must rotate in one direction only, use speed/
frequency limit (
) to achieve this. Do not set parameter
to 0%, as
the drive is then not able to stop correctly.
-300.00%
-600.00…0.00%
Maximum generating power.
1 = 1%
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...