Fault tracing 347
A8BF
ULC underload
warning
Programmable fault:
Selected signal has fallen
below the user underload
curve.
Check for any operating conditions
decreasing the monitored signal (for
example, loss of load if the torque or
current is being monitored).
Check the definition of the load curve
(parameter group
A981
External warning 1
(Editable message text)
Programmable warning:
Fault in external device 1.
Check the external device.
Check setting of parameter
A982
External warning 2
(Editable message text)
Programmable warning:
Fault in external device 2.
Check the external device.
Check setting of parameter
A983
External warning 3
(Editable message text)
Programmable warning:
Fault in external device 3.
Check the external device.
Check setting of parameter
A984
External warning 4
(Editable message text)
Programmable warning:
Fault in external device 4.
Check the external device.
Check setting of parameter
A985
External warning 5
(Editable message text)
Programmable warning:
Fault in external device 5.
Check the external device.
Check setting of parameter
AF88
Season configuration
warning
You have configured a season
which starts before the
previous season.
Configure the seasons with increasing
start dates, see parameters
.
AF8C
Process PID sleep
mode
The drive is entering sleep
mode.
Informative warning. See section
and boost functions for process PID
control
(page
), and parameters
AFAA
Autoreset
A fault is about to be autoreset. Informative warning. See the settings in
parameter group
AFE1
Emergency stop (off2) Drive has received an
emergency stop (mode
selection off2) command.
Check that it is safe to continue
operation. Then return emergency stop
push button to normal position. Restart
drive.
If the emergency stop was
unintentional, check the source
selected by parameter
AFE2
Emergency stop (off1
or off3)
Drive has received an
emergency stop (mode
selection off1 or off3)
command.
Code
(hex)
Warning / Aux. code
Cause
What to do
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...