Fault tracing 345
A780
Motor stall
Programmable warning:
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Check motor load and drive ratings.
Check fault function parameters.
A7AB
Extension I/O
configuration failure
Installed CMOD module is not
the same as configured.
Check that the installed module (shown
by parameter
) is the same as selected by
.
A7C1
FBA A
communication
Programmable warning:
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Check status of fieldbus
communication. See user
documentation of fieldbus interface.
Check settings of parameter groups
.
Check cable connections.
Check if communication master is able
to communicate.
A7CE
EFB comm loss
Programmable warning:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
A7EE
Panel loss
Programmable warning:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Check mounting platform if being used.
Disconnect and reconnect the control
panel.
A88F
Cooling fan
Maintenance timer limit
exceeded.
Consider changing the cooling fan.
Parameter
shows the running time of the cooling
fan.
A8A0
AI supervision
Programmable warning:
An analog signal is outside the
limits specified for the analog
input.
Check signal level at the analog input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
A8A1
RO life warning
The relay has changed states
more than the recommended
number of times.
Change the control board or stop using
the relay output.
0001 Relay output 1
Change the control board or stop using
relay output 1.
0002 Relay output 2
Change the control board or stop using
relay output 2.
0003 Relay output 3
Change the control board or stop using
relay output 3.
Code
(hex)
Warning / Aux. code
Cause
What to do
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...