268 Parameters
See parameter
0.00 h
See parameter
0.00 h
See parameter
0.00 h
See parameter
0.00 h
See parameter
0.00 h
Displays the pumps which can establish connection through
inverter-to-inverter communication.
For example, in a three pump system, drive 1 and drive 2 can
see each other but drive 3 cannot see other drives.
Drive 1 = 0011b, Drive 2 = 0011b, Drive 3 = 0100b
Displays the drives communication loss status.
You can override default communication loss actions by
setting start interlock or constant speed based on the bit
values.
Note:
Bits will reset to zero when communication is restored.
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Descriptions
0
Node 1
Pump 1 is online.
1
Node 2
Pump 2 is online.
2
Node 3
Pump 3 is online.
3
Node 4
Pump 4 is online.
4
Node 5
Pump 5 is online.
5
Node 6
Pump 6 is online.
6
Node 7
Pump 7 is online.
7
Node 8
Pump 8 is online.
8…15
Reserved
Bit
Name
Descriptions
0
Running master in comm loss
The running master drive has lost the
connection to other drives. By default, this drive
continues as a running master.
1
Running follower (master enable)
in comm loss
The running follower drive which is set as
master enabled drive has lost the connection to
other drives. By default, this drive will be a
master (offline).
2
Standby master enabled in comm
loss
The master enabled drive which is in standby
mode has lost the connection to other drives. By
default, this drive remains in standby mode if
already running drives can maintain the process.
3
Standby master disabled in comm
loss
The master disabled drive which is in standby
mode has lost the connection to other drives. By
default, this drive remains in standby mode.
4…15
Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...