186 Parameters
Speed ref ramp out
).
19
Speed ref used
20
Reserved
21
Freq ref used
(page
).
22
Inverter
temperature
23
Process PID output
24
Process PID
feedback
(page
).
25
Process PID
setpoint
(page
26
Process PID
deviation
(page
27
Source selection (see
). -
Defines a filter time constant for the signal monitored by
signal supervision 1.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 1.
0.00
-21474836.00…
21474836.00
Low limit.
-
Defines the upper limit for signal supervision 1.
0.00
-21474836.00…
21474836.00
Upper limit.
-
Defines the hysteresis for the signal monitored by signal
supervision 1.
0.00
0.00…100000.00
Hysteresis.
-
Selects the mode of signal supervision function 2. Determines
how the monitored signal (see parameter
) is compared
to its lower and upper limits (
respectively).
The action to be taken when the condition is fulfilled is
selected by
Disabled
Signal supervision 2 not in use.
0
Low
Action is taken whenever the signal falls below its lower limit. 1
High
Action is taken whenever the signal rises above its upper
limit.
2
Abs low
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
3
Abs high
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
5
Abs both
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...