Parameters 153
Automatic
The drive automatically selects the correct output frequency
to start a rotating motor. This is useful for flying starts: if the
motor is already rotating, the drive will start smoothly at the
current frequency.
Note:
Cannot be used in multimotor systems.
2
Torque boost
The drive pre-magnetizes the motor before the start. The pre-
magnetizing time is defined by parameter
.
Torque boost is applied at start. Torque boost is stopped
when output frequency exceeds 40% of nominal frequency or
when it is equal to the reference value. See parameter
.
This mode should selected if a high break-away torque is
required.
Note:
This mode cannot be used to start into a rotating motor.
WARNING!
The drive will start after the set pre-
magnetizing time has passed even if motor
magnetization is not completed. In applications where
a full break-away torque is essential, ensure that the constant
magnetizing time is long enough to allow generation of full
magnetization and torque.
3
Auboost
Automatic start with torque boost.
Automatic start is performed first and the motor is
magnetized. If the speed is found to be zero, torque boost is
applied.
4
Defines the DC hold frequency, which is used instead of
parameter
when the motor is in scalar
and section
5.00 Hz
0.00…1000.00 Hz
DC hold frequency.
1 = 1 Hz
Defines the start delay. After the conditions for start have
been fulfilled, the drive waits until the delay has elapsed and
then starts the motor. During the delay, warning
is shown.
Start delay can be used with all start modes.
0.00 s
0.00…60.00 s
Start delay
1 = 1 s
Selects the forced current vector rotation mode at low
speeds. When the smooth start mode is selected, the rate of
acceleration is limited by the acceleration and deceleration
ramp times. If the process driven by the permanent magnet
synchronous motor has high inertia, slow ramp times are
recommended.
Can be used for permanent magnet synchronous motors
only.
Disabled
Disabled.
0
Enabled always
Enabled always.
1
Start only
Enabled when starting the motor.
2
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...