168
ACQ550-U1 User’s Manual
• The table below shows the ACQ550 PFC motor assignments for some typical settings in the Relay Output
parameters (1401…1403 and 1410…1412), where the settings are either =31 (
PFC
), or =X (anything but 31), and
where the Autochange function is disabled (8118
AUTOCHNG
INTERV
= 0.0).
• The table below shows the ACQ550 PFC motor assignments for some typical settings in the Relay Output
parameters (1401…1403 and 1410…1412), where the settings are either =31 (
PFC
), or =X (anything but 31), and
where the Autochange function is enabled (8118
AUTOCHNG
INTERV
= value > 0.0).
8118
AUTOCHNG INTERV
Controls operation of the Autochange function and sets the
interval between changes.
• The Autochange time interval only applies to the time when
the speed regulated motor is running.
• See parameter 8119
AUTOCHNG
LEVEL
for an overview of the
Autochange function.
• The drive always coasts to stop when autochange is
performed.
• Autochange enabled requires parameter 8120
INTERLOCKS
=
value > 0.
-0.1 =
TEST
MODE
– Forces the interval to value 36…48 s.
0.0 =
NOT
SEL
– Disables the Autochange function.
0.1…336 – The operating time interval (the time when the start
signal is on) between automatic motor changes.
WARNING!
When enabled, the Autochange function
requires the interlocks (8120
INTERLOCKS
= value > 0)
enabled. During autochange the power output is
interrupted and the drive coasts to stop, preventing
damage to the contacts.
Code Description
Parameter setting
ACQ550 Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
1
4
1
1
1
4
1
2
8
1
1
7
Autochange disabled
RO1
RO2
RO3
RO4
RO5
RO6
31 X X X X X 1
Aux.
X
X
X
X
X
31 31 X X X X 2
Aux.
Aux.
X
X
X
X
31 31 31 X X X 3
Aux.
Aux.
Aux.
X
X
X
X 31 31 X X X 2
X
Aux.
Aux.
X
X
X
X X X 31 X 31 2
X
X
X
Aux.
X
Aux.
31 31 X
X X X 1*
Aux.
Aux.
X
X
X
X
* = One additional relay output for the PFC that is in use. One motor is in “sleep”
when the other is rotating.
Parameter setting
ACQ550 Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
1
4
1
1
1
4
1
2
8
1
1
7
Autochange enabled
RO1
RO2
RO3
RO4
RO5
RO6
31 31 X X X X 1
PFC
PFC
X
X
X
X
31 31 31 X X X 2
PFC
PFC
PFC
X
X
X
X 31 31 X X X 1
X
PFC
PFC
X
X
X
X X X 31 X 31 1
X
X
X
PFC
X
PFC
31 31 X
X
X
X 0**
PFC
PFC
X
X
X
X
** = No auxiliary motors, but the autochange function is in use. Working as a
standard PID-control.
PFC with Autochange mode
ACQ550
Relay logic
Summary of Contents for ACQ550-x1-06A6-2
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...