Grounding
These instructions are for all personnel who are responsible for the electrical
installation, including the grounding of the drive.
WARNING!
Obey these instructions. If you ignore them, injury or death, or
equipment malfunction can occur, and electromagnetic interference can
increase.
• If you are not a qualified electrician, do not do grounding work.
• Always ground the drive, the motor and adjoining equipment to the protective
earth (PE) bus of the power supply. This is necessary for the personnel safety.
Proper grounding also reduces electromagnetic emission and interference.
• Make sure that the conductivity of the protective earth (PE) conductors is
sufficient. See section
on page
. Obey the local
regulations.
• Connect the power cable shields to the protective earth (PE) terminals of the
drive.
• Make a 360° grounding of the power and control cable shields at the cable entries
to suppress electromagnetic disturbances.
Note:
• You can use power cable shields as grounding conductors only when their
conductivity is sufficient.
• Standard IEC/EN 61800-5-1 (section 4.3.5.5.2.) requires that as the normal touch
current of the drive is higher than 3.5 mA AC or 10 mA DC, you must use a fixed
protective earth (PE) connection. In addition,
•
install a second protective earth conductor of the same cross-sectional area
as the original protective earthing conductor,
or
•
install a protective earth conductor with a cross-section of at least 10 mm
2
Cu
or 16 mm
2
Al,
or
•
install a device which automatically disconnects the supply if the protective
earth conductor breaks.
Summary of Contents for ACL30
Page 1: ...ABB high performance elevator drives User s manual ACL30 elevator drive ...
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 34: ...34 Operation principle and hardware description ...
Page 42: ...42 Planning the cabinet installation ...
Page 60: ...60 Planning the electrical installation ...
Page 126: ...126 Using the control panel ...
Page 318: ...318 Maintenance ...
Page 334: ...334 The Safe torque off function ...
Page 338: ...338 Mains chokes ...
Page 342: ...342 EMC filters ...
Page 348: ...Dimension drawings 348 Frame size B D1 D2 W H1 H2 ...
Page 349: ...Dimension drawings 349 ...
Page 350: ...Dimension drawings 350 Frame size C D1 D2 H2 H1 W ...
Page 351: ...Dimension drawings 351 ...
Page 352: ...Dimension drawings 352 Frame size D ...
Page 354: ...354 Dimension drawings EMC filters JFI 0x ...
Page 356: ...356 Dimension drawings Brake resistors JBR xx ...
Page 358: ...358 Dimension drawings ...