90
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Mailbox read/write
The ACH580 provides a “Mailbox” function to access parameters that have not been
pre-defined by the protocol. Using mailbox, any drive parameter can be identified
and read. Mailbox can also be used to adjust parameter settings by writing a value to
any parameter identified. The following table describes the use of this function.
Actual value scaling
When using Modbus, the scaling of actual values is set by the parameter resolution.
(Refer to the
Parameter list and descriptions
section in the
ACH580 HVAC control
program firmware manual
(3AXD50000027537) for parameter resolutions.) For
example:
Name
Description
Protocol Reference
Modbus
1)
N2
BACnet
Mailbox
Parameter
Enter the number of the drive group and
parameter number using the format:
(group #) * 256 + parameter #.
Example: drive parameter 28.01 is entered as
(28 * 256) + 1 = 7169
Does not
apply.
AO19
AV25
Mailbox Data
Contains the parameter value after a read, or
enter the desired parameter value for a write.
AO20
AV26
Mailbox Read A binary value triggers a read – the value of
the “Mailbox Parameter” appears in “Mailbox
data”.
BO19
BV15
Mailbox Write
A binary value triggers a write – the drive
value for the “Mailbox Parameter” changes to
the value in “Mailbox data”.
BO20
BV16
1) Modbus provides direct access to all parameters using the format: (group #) * 256
+ parameter #.
Example: drive parameter 28.01 is mapped as 40000 + 28 * 256 + 1 = 407169.
Feedback Integer
Scaling
(Feedback Integer) / (Scaling) = Scaled Value
100 (example: 12.11 AI1 actual
feedback)
1000 = 1 unit
100 / 1000 = 0.1 mA
10
10 = 1%
10 / 10 = 1%
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......