If the protective earth conductor is routed through a plug and socket, or similar
means of disconnection, it must not be possible to disconnect it unless power is
simultaneously removed.
Note: You can use power cable shields as grounding conductors only when their
conductivity is sufficient.
■
Additional grounding requirements – UL (NEC)
This section gives grounding requirements according to standard UL 61800-5-1.
The protective earth conductor must be sized as specified in Article 250.122 and
table 250.122 of the National Electric Code, ANSI/NFPA 70.
For cord-connected equipment, it must not be possible to disconnect the protective
earth conductor before power is removed.
Selecting the control cables
■
Shielding
Only use shielded control cables.
Use a double-shielded twisted pair cable for analog signals. ABB recommends this
type of cable also for the pulse encoder signals. Use one individually shielded pair
for each signal. Do not use common return for different analog signals.
A double-shielded cable (a) is the best alternative for low-voltage digital signals,
but single-shielded (b) twisted pair cable is also acceptable.
a
b
■
Signals in separate cables
Run analog and digital signals in separate, shielded cables. Do not mix 24 V DC
and 115/230 V AC signals in the same cable.
■
Signals that can be run in the same cable
If their voltage does not exceed 48 V, relay-controlled signals can be run in the
same cables as digital input signals. The relay-controlled signals should be run as
twisted pairs.
74 Guidelines for planning the electrical installation
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...