ACH580 Installation, Operation and Maintenance Manual
81
ACH580-01 Installation
0002
Maximum speed limit
or calculated field
weakening point too
low.
Check settings of parameters
30.11 Minimum speed
30.12 Maximum speed
99.07 Motor nominal voltage
99.08 Motor nominal frequency
99.09 Motor nominal speed
.
Make sure that
30.12
> (0.55
×
99.09
) >
(0.50
×
synchronous speed)
30.11
< 0, and
supply voltage > (0.66 ×
99.07
).
0003
Maximum torque limit
too low.
Check settings of parameter
99.12
Motor nominal torque
, and the torque
limits in group
30 Limits
.
Make sure that the maximum torque
limit in force is greater than 100%.
0004
Current measurement
calibration did not finish
within reasonable time
Contact your local ABB
representative.
0005…0008
Internal error.
Contact your local ABB
representative.
0009
(Asynchronous motors
only)
Acceleration did not
finish within reasonable
time.
Contact your local ABB
representative.
000A
(Asynchronous motors
only)
Deceleration did not
finish within reasonable
time.
Contact your local ABB
representative.
000B
(Asynchronous motors
only)
Speed dropped to zero
during ID run.
Contact your local ABB
representative.
000C
(Permanent magnet
motors only)
First acceleration did
not finish within
reasonable time.
Contact your local ABB
representative.
000D
(Permanent magnet
motors only)
Second acceleration
did not finish within
reasonable time.
Contact your local ABB
representative.
000E…0010
Internal error.
Contact your local ABB
representative.
0011
(Synchronous
reluctance motors only)
Pulse test error.
Contact your local ABB
representative.
Code
(hex)
Fault / Aux. code
Cause
What to do
ACH580_Inst_Op_Maint_Rev G.book Page 81