ACH550-UH User’s Manual
1-85
Parameters
0144
DRIVE ON TIME LO
00:00:00…23:59:58
1 = 2 s
-
The drive’s accumulated power-on time in 2 second ticks (30 ticks = 60 seconds).
• Shown in format hh.mm.ss.
• Cannot be reset.
0145
MOTOR TEMP
Par. 3501 = 1…3:
1
-
-10…200 °C
Par. 3501 = 4: 0…5000 ohm
Par. 3501 = 5…6: 0…1
Motor temperature in degrees Celsius / PTC resistance in ohms.
• Applies only if motor temperature sensor is set up.
• See parameter 3501.
0150
CB TEMP
-20.0…150.0 °C
1.0 °C
-
Temperature of the drive control board in degrees Celsius.
Note:
Some drives have a control board (OMIO) that does not support this feature. These drives always show the
constant value of 25.0 °C.
0153
MOT THERM STRESS
0.0…100.0%
0.1%
-
Estimated rise of the motor temperature. Value equals to the estimated motor thermal stress as a percentage of the
motor temperature trip level.
0158
PID COMM VALUE 1
-32768…+32767
1
-
Data received from fieldbus for PID control (PID1 and PID2).
0159
PID COMM VALUE 2
-32768…+32767
1
-
Data received from fieldbus for PID control (PID1 and PID2).
0174
SAVED KWH
0.0…999.9 kWh
0.1 kWh
-
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply. See the note
on page
• The counter value is accumulated till it reaches 999.9 after which the counter rolls over and starts again from 0.0.
• Can be reset with parameter 4509
ENERGY
RESET
(resets all energy calculators at the same time).
• See
.
0175
SAVED MWH
0…65535 MWh
1 MWh
-
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply. See the note
on page
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Can be reset with parameter 4509
ENERGY
RESET
(resets all energy calculators at the same time).
• See
.
0176
SAVED AMOUNT 1
0.0…999.9
0.1
-
Energy saved in local currency (remainder when the total saved energy is divided by 1000). See the note on
page
.
• To find out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the
value of parameter 0176.
Example:
0176
SAVED
AMOUNT
1 = 123.4
0177
SAVED
AMOUNT
2 = 5
Total saved energy = 5 · 1000 + 123.4 = 5123.4 currency units.
• The counter value is accumulated till it reaches 999.9 (the counter does not roll over).
• Can be reset with parameter 4509
ENERGY
RESET
(resets all energy calculators at the same time).
• Local energy price is set with parameter 4502
ENERGY
PRICE
.
• See
.
Group 01: Operating Data
Code Description Range
Resolution
Default
S
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......