Chapter 4 – Programming
4-10
ACS/ACH 400 Direct N2 Bus Interface
FL10 PANEL LOSS
Panel loss. Panel is disconnected when Start/Stop/Dir or
reference is coming from panel. See parameter 3002 and
APPENDIX.
Note! If FL10 is active when the power is turned off, the
ACS/ACH 400 will start in remote control (REM) when the
power is turned back on.
FL11 PARAMETERING
Parameters inconsistent. Possible fault situations:
•
MINIMUM
AI1 >
MAXIMUM
AI1 (parameters 1301 and
1302)
•
MINIMUM
AI2 >
MAXIMUM
AI2 (parameters 1304 and
1305)
•
MINIMUM
FREQ
>
MAXIMUM
FREQ
(parameters 2007 and
2008)
FL12 MOTOR STALL
Motor stall. See parameter 3009
STALL
FUNCTION
.
FL13 SERIAL COMM
LOSS
Serial communication loss.
FL14 EXTERNAL
FAULT SIGNAL
External fault is active. See parameter 3003
EXTERNAL
FAULT
.
FL15
*
OUTPUT EARTH
FAULT
Output ground fault.
FL16
*
DC BUS RIPPLE
DC bus ripple too high. Check power supply for phase
loss or imbalance.
FL17 UNDERLOAD
Underload.
FL18
Reserved.
FL19 DDCS LINK
DDCS link fault.
FL20
-
FL28
*
HARDWARE
ERROR
Hardware error. Contact the factory.
“COMM LOSS” (ACS-PAN) Serial link failure. Bad connection between the control
panel and the ACS/ACH 400.