3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or PNIO = module type (2 = DO); COM1/COM2:
1..10 = expansion 1..10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
LED
State
Color
LED = OFF
LED = ON
Outputs
O0...O7
Digital output Yellow
Output is
OFF
Output is ON
(the output voltage is
only displayed if the
supply voltage of the
module is ON)
Technical data
The System Data of AC500-eCo apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Parameter
Value
Process supply voltage L+
Connections
Terminal 20 for L+ (+24 V DC). The negative
pole is provided by the I/O bus.
Rated value
24 V DC
Current consumption via L+
50 mA
Inrush current (at power-up)
0.0035 A
²
s
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse for UP
Recommended; the outputs must be pro-
tected by a 3 A fast-acting fuse
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of the
CPU/communication interface module
Ca. 5 mA
Galvanic isolation
Yes, between the output group and the rest
of the module
Isolated groups
2 (4 channels per group)
Surge-voltage (max.)
35 V DC for 0.5 s
Max. power dissipation within the module
2.0 W
Weight
Ca. 150 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US