Alarm and Events
Section 3 Configuration
60
3BSE037076-510 D
Alarm Hiding
Alarm hiding should be configured in the provider system. Alarms hidden in the
provider will show up in a hidden alarm list in the subscriber system. It is however
not possible to show the corresponding hiding rule in the subscriber for a hidden
alarm, since the hiding rule only exists in the provider.
Alarm Shelving
Alarm shelving configuration is done in library structure in both provider and
subscriber systems. For a consistency behavior it is recommended that shelving
configuration conforms for provider and subscriber.
Audible Alarms/Global Silence
Global silence is a function which allows an operator on one workplace to silence an
alarm on all workplaces. If global silence is used with Multisystem Integration, a
silence operation made in the provider will also affect the subscriber and vice versa.
Feature Pack Functionality______________________________________________________________________
Point of Control Support
This section applies to the System 800xA 5.1 Feature Pack release only.
Point of Control is a concept that allows division of the plant into sections. The
operator controlling a section is called the Responsible User. The Responsible User
has all access rights for the section. A typical scenario is that only the Responsible
User will be able to control the process in this section.
Using Point of Control with Multisystem Integration, the responsibility can be taken
locally on the provider system, and remotely on the subscriber system. For more
information on the Point of Control function, refer to
Point of Control
section
in
System 800xA Administration and Security (3BSE037410*)
.
The responsibility can be transferred between the provider systems located within
the plant area and also between the provider system and the subscriber system.
Summary of Contents for Ability 800xA Series
Page 2: ......
Page 3: ...System 800xA Multisystem Integration System Version 5 1...
Page 18: ...Prerequisites and Requirements Section 1 Introduction 18 3BSE037076 510 D...
Page 26: ...Medium Large Configuration Section 2 Installation 26 3BSE037076 510 D...
Page 74: ...Limitations Section 3 Configuration 74 3BSE037076 510 D...
Page 98: ...Upgrade Procedure Section 5 Maintenance 98 3BSE037076 510 D...
Page 106: ...Appendix A Error Messages 106 3BSE037076 510 D...
Page 112: ...No System Alarm in the Provider System Appendix B Fault Tracing 112 3BSE037076 510 D...
Page 116: ...Index 116 3BSE037076 510 D Index 116 3BSE037076 510 D...
Page 120: ...Updates in Revision Index D 120 3BSE037076 510 D...
Page 121: ......