QUICK START GUIDE
Page 6
Version 6.0
© 2021 ABB. All rights reserved.
Step 4
-
Connect AC Input
AC Input box location: Bottom Feed
-
bottom left Top Feed
-
top left
AC knockouts: for
2”
conduit.
Danger:
Shock Hazard
-
Turn OFF and lock
-
out tag
-
out the AC source before making AC connections.
When connecting to AC mains, follow all local and national wiring rules.
Caution:
Ensure that wires do not come in contact with sharp or rough surfaces that may damage insulation and
cause a short circuit.
1.
Verify all AC breakers are off
-
Charger AC1 and external AC feed breaker.
2.
Choose the next step to match AC input voltage marked on the charger ratings label.
Step 3
-
Ground the Chassis
Chassis ground lug
-
1/4”
on
5/8”
centers (lug provided).
Minimum 6 AWG recommended.
1.
Connect ground wire to chassis on top or bottom of cabinet.
1/4
-
20 screws (2) provided
Torque to 65 in
-
lb (7.3 Nm) using a
7/16”
socket wrench.
AC Input per Charger Label
AC Input Option
Follow Step
120/240
AC
Step 4A Single Phase
200/240
AC
Step 4B Three Phase
Screw
Wire Entry
Ground Wire
Lug
Screw
Bottom Feed
Terminal Block for Single AC Feed shown
Top Feed
Terminal Block for Single AC Feed shown
Ground
Bar
Top Feed
Chassis Ground Lug
(top or bottom)