QUICK START GUIDE
Page 19
Version 6.0
© 2021 ABB. All rights reserved.
Information: Pulsar XL Controller Alarm Relay Jumpers
Jumpers are located on the side top of the controller.
Alarm Relay Jumper Factory Defaults are Open On Alarm.
1.
Remove Controller
-
2 thumb screws.
2.
Position jumpers per site engineering instructions
3.
Replace controller
-
secure with 2 thumb screws.
Information: Pulsar XL Controller
-
LAN Port
-
Local / Network
The LAN port is be configured as Local or Network
-
controller display menu path Configuration > Communication Ports > Network Settings >
DHCP > mode CLIENT or SERVER
Local
(Server): LAN connects to a laptop.
Local (Server) is a temporary setting. When configuration is complete, return LAN
port to Network (Client) mode.
Network
(Client): LAN connects to a network. (Default).
CAUTION:
Do not connect LAN port to a network when configured as Local.
See Pulsar Plus G3 Controller Product Manual for details.
Information: Pulsars XL (IP843G) Controller Basic Operation
View and change system parameters from the factory defaults via
A.
Controller Display
B. Craft Port on front of controller using a laptop with EasyView2 software or HyperTerminal.
EasyView2 (GUI) software can be downloaded from
https://abbpowerconversion.com
C. J5 LAN port web pages using a laptop with browser. LAN port Server mode is for local laptop connection. Set
the LAN port to Server: With the controller set to Server enter the default IP address 192.168.2.1 (default) in the
web browser address field.
Warning:
Do not connect J5 LAN port to a network when set to Server. Set the controller to Client or Static before
connecting to the network. Static is the factory default setting and the typical setting for most networks.
Controller Alarm Status: The display changes colors; Green = Normal, Amber = Minor Alarm, Red = Critical/Major
Alarm