Mounting / Installation
Pos: 33 /Busch-Jaeger (Neustruktur)/Modul-Struktur/Online-Dokumentation/Sicherheit (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - Niederspannungs- und 230 V-Leitungen @ 18\mod_1302617821491_15.docx @ 103465 @ @ 1
Warning
E lec tric voltage!
Risk of death and fire due to electrical voltage of 230 V.
– Low-voltage and 230 V cables must not be installed together in a flush-mounted socket!
In case of a short-circuit there is the danger of a 230 V load on the low-voltage line.
Pos: 34 /Busch-Jaeger (Neustruktur)/Modul-Struktur/Online-Dokumentation/Sicherheit (--> Für alle Dokumente <--)/Warnhinweise/Sicherheit - Fachkenntnisse @ 18\mod_1302774384017_15.docx @ 103564 @ 2 @ 1
7.1
R equirements for the elec tric ian
Warning
E lec tric voltage!
Install the device only if you have the necessary electrical engineering knowledge and experience.
•
Incorrect installation endangers your life and that of the user of the electrical system.
•
Incorrect installation can cause serious damage to property, e.g. due to fire.
The minimum necessary expert knowledge and requirements for the installation are as follows:
•
Apply the "five safety rules" (DIN VDE 0105, EN 50110):
1.
Disconnect from power;
2.
Secure against being re-connected;
3.
Ensure there is no voltage;
4.
Connect to earth;
5.
Cover or barricade adjacent live parts.
•
Use suitable personal protective clothing.
•
Use only suitable tools and measuring devices.
•
Check the type supply network (TN system, IT system, TT system) to secure the following
power supply conditions (classic connection to ground, protective earthing, necessary
additional measures, etc.).
Pos: 35 /DinA4 - Anleitungen Online/Inhalt/KNX/DoorEntry/Montage/Montagehinweise - Allgemein @ 19\mod_1310563670478_15.docx @ 107743 @ 2 @ 1
7.2
G eneral ins tallation ins truc tions
•
Terminate all branches of the wiring system via a connected bus device (e.g., indoor station, outdoor station,
system device).
•
Do not install the system controller directly next to the bell transformer and other power supplies (to avoid
interference).
•
Do not install the wires of the system bus together with 230 V wires.
•
Do not use common cables for the connecting wires of the door openers and wires of the system bus.
•
Avoid bridges between different cable types.
•
Use only two wires for the system bus in a four-core or multi-core cable.
•
When looping, never install the incoming and outgoing bus inside the same cable.
•
Never install the internal and external bus inside the same cable.