Function name
Signal type
Signal name
Description
Motor startup supervision
(STTPMSU)
Analog inputs
STTPMSU.1.START_CNT
Number of motor start-ups
occurred
Binary inputs
STTPMSU.1.MOT_START
Signal to show that motor
startup is in progress
STTPMSU.1.OPR_IIT
Operate/trip signal for thermal
stress.
STTPMSU.1.LOCK_START
Lock out condition for restart of
motor.
STTPMSU.1.OPR_STALL
Operate/trip signal for stalling
protection.
Phase reversal (PREVPTOC)
Binary inputs
PREVPTOC.1.START
Started signal
PREVPTOC.1.OPERATE
Operated signal
Loss of load supervision
(LOFLPTUC)
Binary inputs
LOFLPTUC.1.START
Loss of load protection started
LOFLPTUC.1.OPERATE
Loss of load protection operated
Motor stall protection
(JAMPTOC)
Binary inputs
JAMPTOC.1.START
Started signal
JAMPTOC.1.OPERATE
Operated
Negative-phase-sequence time
overcurrent protection
(MNSPTOC)
Binary inputs
MNSPTOC.1.START
Started
MNSPTOC.1.OPERATE
Operated
MNSPTOC.1.BLK_RESTART
Signal for blocking reconnection
of an overheated machine
Tap position indication
(TPOSSLTC)
Analog inputs
TPOSSLTC.1.TAP_POS
Tap position value as integer
Binary inputs
TPOSSLTC.1.TAP_POS_IV
TAP_POS invalidity status
Three-phase inrush current
detector (INRPHAR)
Binary inputs
INRPHAR.1.BLK2H
Second harmonic based block
INRPHAR.1.BLK2H_A
Second harmonic based block,
phase A
INRPHAR.1.BLK2H_B
Second harmonic based block,
phase B
INRPHAR.1.BLK2H_C
Second harmonic based block,
phase C
Transient/intermittent earth-fault
(INTRPTEF)
Binary inputs
INTRPTEF.START
Start signal
INTRPTEF.OPERATE
Operate signal
INTRPTEF.BLK_EF
Block signal for EF to indicate
opposite direction peaks
Versatile Switch (VSGGIO)
Binary inputs
VSGGIO.1.POS1
Position 1 indication, logical
signal
VSGGIO.1.POS2
Position 2 indication, logical
signal
Double bit indications
VSGGIO.1.POSITION
Position indication, integer
1MRS756791 A
Section 2
DNP3 data mappings
630 series
39
Point List Manual