Section 4
1MAC050144-MB C
Protection functions
370
615 series ANSI
Technical Manual
4.6.2.8
Monitored data
Table 326: 87T Monitored data
Name
Type
Values (Range)
Unit
Description
OPR_A
BOOLEAN
0=False 1=True
Trip phase A
OPR_B
BOOLEAN
0=False 1=True
Trip phase B
OPR_C
BOOLEAN
0=False 1=True
Trip phase C
BLKD2H_A
BOOLEAN
0=False 1=True
2nd harmonic restraint block phase
A status
BLKD2H_B
BOOLEAN
0=False 1=True
2nd harmonic restraint block phase
B status
BLKD2H_C
BOOLEAN
0=False 1=True
2nd harmonic restraint block phase
C status
BLKD5H_A
BOOLEAN
0=False 1=True
5th harmonic restraint block phase
A status
BLKD5H_B
BOOLEAN
0=False 1=True
5th harmonic restraint block phase
B status
BLKD5H_C
BOOLEAN
0=False 1=True
5th harmonic restraint block phase
C status
BLKDWAV_A
BOOLEAN
0=False 1=True
Waveform blocking phase A status
BLKDWAV_B
BOOLEAN
0=False 1=True
Waveform blocking phase B status
BLKDWAV_C
BOOLEAN
0=False 1=True
Waveform blocking phase C status
2nd harmonic block
BOOLEAN
0=False 1=True
2nd harmonic restraint block
2nd harmonic block
phaseA
BOOLEAN
0=False 1=True
2nd harmonic restraint block phase
A
2nd harmonic block
phaseB
BOOLEAN
0=False 1=True
2nd harmonic restraint block phase
B
2nd harmonic block
phaseC
BOOLEAN
0=False 1=True
2nd harmonic restraint block phase
C
5th harmonic block
BOOLEAN
0=False 1=True
5th harmonic restraint block
5th harmonic block phase
A
BOOLEAN
0=False 1=True
5th harmonic restraint block phase
A
5th harmonic block phase
B
BOOLEAN
0=False 1=True
5th harmonic restraint block phase
B
5th harmonic block phase
C
BOOLEAN
0=False 1=True
5th harmonic restraint block phase
C
Connection group
compensated primary
current phase A
FLOAT32
0.00...40.00
xIn
Connection group compensated
primary current phase A
Connection group
compensated primary
current phase B
FLOAT32
0.00...40.00
xIn
Connection group compensated
primary current phase B
Connection group
compensated primary
current phase C
FLOAT32
0.00...40.00
xIn
Connection group compensated
primary current phase C
Connection group
compensated secondary
current phase A
FLOAT32
0.00...40.00
xIn
Connection group compensated
secondary current phase A
Table continues on next page
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......